ICT Campus Bettembourg DC 1.2
Street Adress: 4, rue A.Graham Bell, L-3235 Bettembourg
Specifications
Operational since | January 2011 |
Design | Tier IV |
Gross Size | 4.500 m² |
Net Size | 1.300 m² |
Power available | 2 x 6,3 MVA |
IT room height | 3,80 m |
Raised floor | 1,00 m |
Floor load | 2.000 kg/m² |
Equipment elevator | 2.500 kg/m² |
UPS systems | Redundant 2*(N+1) |
Generator autonomy | 48 hours; 24/365 refuel contracts |
Power to IT rooms | Average 2.300 W/m² |
Power loads | up to 10 kW/m² |
Cooling redundancy | 2*N |
Cooling specifications | Water input 10°C; output 15°C |