(Translated by https://www.hiragana.jp/)
IEC 60038 - Wikipedia Jump to content

IEC 60038

From Wikipedia, the free encyclopedia
IEC voltage range AC RMS
voltage
(V)
DC voltage (V) Defining risk
High voltage > 1,000 > 1,500 Electrical arcing
Low voltage 50 to 1,000 120 to 1,500 Electrical shock
Extra-low voltage < 50 < 120 Electrical fire

International Standard IEC 60038, IEC standard voltages, defines a set of standard voltages for use in low voltage and high voltage AC and DC electricity supply systems.

Low voltage

[edit]

Where two voltages are given below separated by "/", the first is the root-mean-square voltage between a phase and the neutral connector, whereas the second is the corresponding root-mean-square voltage between two phases (exception: the category shown below called "One Phase", where 240 V is the root-mean-square voltage between the two legs of a split phase). The three-phase voltages are for use in either four-wire (with neutral) or three-wire (without neutral) systems.

Three-phase 50 Hzへるつ

[edit]
  • 230 V / 400 V (formerly 220/380 V)
  • 400 V / 690 V (formerly 380/660 V)
  • 1000 V phase to phase (3 wire)

Suppliers using 220 V / 380 V or 240 V / 415 V systems were expected by the standard to migrate to the recommended value of 230 V / 400 V by the year 2003. This migration has already been largely completed, at least within the European Union.

Voltage conversion schedule

[edit]
Year Neutral-Phase [V] / Phase-Phase [V] Tolerances[1]
— 1987 220 V / 380 V – 10% .. + 10%
1988 — 2003 230 V / 400 V – 10% .. + 6%
2003 — 230 V / 400 V – 10% .. + 10%

Three-phase 60 Hzへるつ

[edit]
  • 120 V / 208 V
  • 240 V
  • 230 V / 400 V
  • 277 V / 480 V
  • 480 V
  • 347 V / 600 V
  • 600 V / 1000 V

One-phase, three-wire 60 Hzへるつ (American split-phase)

[edit]
  • 120 V / 240 V

Table 3 1 kV to 35 kV

[edit]

Table 3 of IEC 60038 lists nominal voltages above 1 kV and not exceeding 35 kV. There are two series, one from 3 kV up to 35 kV

Table 4 35 kV - 230 kV

[edit]

Table 4 shows nominal voltages above 35 kV and not exceeding 230 kV.

Table 5 245 - 1,200 kV

[edit]

Table 5 is systematically different, as the highest voltage for equipment is the characteristic value exceeding 245 kV. The enumeration begins at 300 kV and ends with 1200 kV.

See also

[edit]

References

[edit]
[edit]