Specifications

Operational since June 2009
     
Design Tier IV Design Certified  
     
Gross Size 10.000 m²
Net Size 3.100 m²
   
Power available 2 x 6,3 MVA
   
IT room height 3,80 m
Raised floor 1,00 m
Floor load 1.500 kg/m²
Equipment elevator 4.000 kg/m²
   
UPS systems Redundant 2*(N+1)
   
Generator autonomy 48 hours; 24/365 refuel contracts
   
Power to IT rooms Average 1.150 W/m²
   
Power loads up to 5 kW/m²
   
Cooling redundancy 2*N
Cooling specifications Water input 10°C; output 15°C

 