ICT Campus Bettembourg DC 1.1
Street Adress: 4, rue A.Graham Bell, L-3235 Bettembourg
GPS Localisation: CR161a L-3235 Bettembourg
Specifications
Operational since | June 2009 | |
Design | Tier IV Design Certified | |
Gross Size | 10.000 m² | |
Net Size | 3.100 m² | |
Power available | 2 x 6,3 MVA | |
IT room height | 3,80 m | |
Raised floor | 1,00 m | |
Floor load | 1.500 kg/m² | |
Equipment elevator | 4.000 kg/m² | |
UPS systems | Redundant 2*(N+1) | |
Generator autonomy | 48 hours; 24/365 refuel contracts | |
Power to IT rooms | Average 1.150 W/m² | |
Power loads | up to 5 kW/m² | |
Cooling redundancy | 2*N | |
Cooling specifications | Water input 10°C; output 15°C |